JOWA REP-1L sterilises drinking water with one low-pressure UV lamp in a stainless steel chamber. A photocell measures UV intensity and gives an alarm and closes the outlet solenoid valve when it falls below 30 %; a lamp ammeter monitors the lamp. It is fitted after the pH filter, storage tank and hydrophore, as close to the tapping point as possible. The manual covers specification, installation, start-up, chamber cleaning, lamp and quartz jacket replacement, a troubleshooting chart, wiring and parts.
Apkopes procedūras
Replacing a quartz jacket
- Switch off the operating switch and the automatic fuse; drain the chamber. 14. lpp.
- Remove the wing nuts and end covers, disconnect the lamp and pull it out. 14. lpp.
- Remove the O-ring flange (three 6 mm socket screws), slide the quartz out on a 10–18 mm wooden or plastic rod. 14. lpp.
- Fit new O-rings (soap inside), wipe the quartz with alcohol and do not touch it with bare hands. 14. lpp.
- Slide the new quartz in on the rod, refit flanges hand-tight to bottom, pressurise and check for leaks; refit lamp and covers. 14. lpp.
Bojājumi un ko darīt
Tehniskie parametri
| UV lamp | 1 low-pressure lamp, 158 cm, 65 W (27 W at 253.7 nm) | 3. lpp. |
|---|---|---|
| UV dose | > 35 000 µWs/cm² at 2.7 m³/h, 60 % transmission | 3. lpp. |
| Capacity | 2.7–5.4 m³/h depending on water quality | 3. lpp. |
| Intensity alarm | below 30 % | 3. lpp. |
| Power | 150 W, 230 V 50/60 Hz | 3. lpp. |
| Working pressure | up to 10 bar | 3. lpp. |
| Chamber | SS 316, 1630 × 104 × 275 mm, 16 kg | 3. lpp. |
| Lamp voltage (unlit) | about 600 V for 152 cm lamp | 16. lpp. |
Avots: ražotāja rokasgrāmata “EM-26 RE-UV-PURIFIERS”, 21 lpp. Lappušu numuri atbilst oriģinālam. Pirms darba pārbaudiet rokasgrāmatu uz kuģa.